IOGP Safety Alert #284
IOGP SAFETY ALERT |
INCORRECT PRESSURE GAUGE ON HIGH PRESSURE SUPPLY LINE |
Country: UK – Europe |
Location: — |
Incident Date: 3 September 2015 Time: 09:00 |
Type of Activity: Maintenance, inspection, testing |
Type of Injury: Pressure release |
Function: Production |
When re-commissioning a Steam Turbine following maintenance, a small steam leak was observed from a pressure gauge located on the high pressure steam supply. The pressure gauge was rated to one Bar(g) and the safety seal failed when it was exposed to 55 Bar(g) steam during re-commissioning. The pressure gauge in question was brand new and had been fitted during the recent maintenance period. |
What Went Wrong?:
Figure 1 – Correct pressure gauge (Bar) Figure 2 – Incorrect Pressure Gauge (%) |
Corrective Actions and Recommendations:
|
Source: https://safetyzone.iogp.org